Alpine Supply Company 36 Direct Vent Gas Fireplace
VENTING REQUIREMENTS
VENTING REQUIREMENTS – HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT SYSTEM
(FOR BOTH PROPANE AND NATURAL GAS)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90 deg. Elbow.
A vent guard (part # 09364) should be used whenever the termination is lower than the specified minimum
of your local building codes.
Firestops are required at each floor level and whenever passing through a wall.
All ASC-36 fireplaces use Simpson 4” x 6 5/8” venting. Other Simpson sizes are not approved for use with
the ASC-36.